- Single space rack mount power distributor w/stage 2 surge and spike protection.
- Nominal line voltage: 120 VAC
- Maximum line current: 15 Amps
- Maximum allowable voltage: 125 VAC (RMS)
-Maximum continuous voltage differential applied between line
and neutral, line and ground, or neutral and ground
- Protection mode: Line to Neutral
- Peak impulse current (8/20 micro seconds):
-30,000 Amps, one time
-19,500 Amps, two times within 5 minutes
-7,000 Amps, ten times within 2 minutes
- Maximum peak impulse current pulse as defined between line
and neutral
- Maximum multiple impulse current derated per spec
- Maximum clamping voltage: 545 Volts @ 100 Amps
- Response time: Instantaneous (Less than 1 nanosecond)
- EMI/RF Suppression: More than 20 db
-Calculated line to neutral, 100 KHz to 1 MHz suppression based upon
nominal impedance
- Surge energy dissipation: 711 Joules (10 / 100 micro seconds)
- 2 stage surge suppression with status indicators
- Surge suppression circuit does not contaminate ground
Size (ID):
1.75" (1 space)